Physical AIUpdated 21 October 20268 min read

VFD Guide: How Variable Frequency Drives Control Motors

A variable frequency drive (VFD) controls an AC motor's speed by changing the frequency and voltage it supplies. On fans and pumps, power falls with the cube of speed, so the Carbon Trust says a 20% speed reduction can save around 50% of power. Modern VFDs are typically 92 to 95% efficient.

VFDMotor DrivesMotor ControlEnergy EfficiencyInvertersIndustrial Automation
Man working on a laptop at a desk in a teal-walled room

Key takeaways

  • A VFD has three stages (rectifier, DC link, inverter) and varies motor speed by changing output frequency and voltage.
  • The Carbon Trust (CTG006) states a 20% speed reduction on a fan or pump gives about a 50% power saving.
  • Worked example: a 15 kW fan at 80% speed draws about 7.7 kW (15 x 0.512), roughly 29,000 kWh saved over 4,000 hours.
  • Typical VSD efficiency is 92 to 95%, and it falls at light motor load (US DOE Tip Sheet 11).
  • Keep voltage proportional to frequency: a 400 V, 50 Hz motor needs about 320 V at 40 Hz.

A variable frequency drive (VFD), also called an inverter or variable speed drive, controls an AC induction motor by varying the frequency and voltage it receives. Because motor speed follows supply frequency, the drive gives you smooth starts, adjustable speed and, on fans and pumps, large energy savings. The Carbon Trust's variable speed drives guide (CTG006) says that on variable-torque loads a 20% speed reduction results in a 50% power saving.

How does a VFD work?

A VFD converts fixed-frequency AC to DC and then synthesises variable-frequency AC. Wikipedia describes the controller as three sub-systems: a rectifier bridge converter, a DC link and an inverter.

  1. Rectifier: converts incoming AC to DC.
  2. DC link: smooths the DC with capacitors (and sometimes inductors).
  3. Inverter: switches the DC with IGBT transistors using pulse width modulation (PWM) to build a three-phase output of chosen frequency and voltage.

Motor speed is tied to frequency. Synchronous speed in rpm is 120 x frequency / number of poles, so a four-pole motor on 50 Hz is 1,500 rpm and at 40 Hz it is 1,200 rpm (Wikipedia, Induction motor). To keep the motor's magnetic flux constant, the drive keeps voltage roughly proportional to frequency, the V/Hz relationship. For a 400 V, 50 Hz motor that is 8 V per Hz, so at 40 Hz the drive supplies about 320 V. Wikipedia's example for a 460 V, 60 Hz motor is 7.67 V/Hz.

A small variable frequency drive with a cooling fan, power terminals and control terminal block
A small variable frequency drive with a cooling fan, power terminals and control terminal blockPhoto: Suyash.dwivedi, CC BY-SA 4.0, via Wikimedia Commons

This video shows the stages of a drive in detail.

Variable Frequency Drives Explained - VFD Basics IGBT inverter

How much energy can a VFD save?

On centrifugal fans and pumps, a lot, because power varies with the cube of speed. Under the affinity laws, power is proportional to speed cubed, assuming constant efficiency (Wikipedia, Affinity laws). The Carbon Trust guide gives the rule of thumb: on variable-torque loads such as fans and pumps, any speed reduction saves large amounts of energy, and a 20% speed reduction gives a 50% power saving.

A worked example in plain text: a fan draws 15 kW at full speed. At 80% speed, power = 15 x 0.8 x 0.8 x 0.8 = 15 x 0.512 = 7.7 kW, a saving of about 7.3 kW. Over 4,000 operating hours a year that is roughly 29,000 kWh. The calculation holds when the fan or pump is truly centrifugal and the system has no large static head; a pump lifting water against a high static head saves less because the curve is not a pure cube law.

Constant-torque loads such as conveyors behave differently: the Carbon Trust notes that a 50% speed reduction means 50% less power, which is a direct proportion rather than a cube. Drives also have their own losses. The same guide says VSDs are typically 92 to 95% efficient, and the US Department of Energy notes that drive efficiency falls as motor load drops (Motor Systems Tip Sheet 11).

Load typeExamplesPower vs speedSaving potential
Variable torqueCentrifugal fans, pumpsPower rises with speed cubedVery large
Constant torqueConveyors, positive-displacement pumps, hoistsPower proportional to speedModerate
Constant powerWinders, machine-tool spindlesTorque falls as speed risesApplication dependent

What else do VFDs improve besides energy use?

A VFD improves process control and mechanical life as well as energy use. The practical benefits are:

  • Soft start and stop: controlled acceleration and deceleration ramps reduce mechanical stress on belts, gears and couplings.
  • Process control: the drive can take a speed reference from a PLC or from a PID loop, for example holding a pump to a pressure setpoint. See our PID control guide.
  • Less throttling: speed control replaces dampers and throttle valves, which waste energy as heat.
  • Power factor: the Carbon Trust lists improved power factor among the benefits, because more of the supply current drives the load.
  • Motor protection: overload, overcurrent and phase-loss detection are usually built in.

How do you commission a VFD?

Enter the motor data, set the ramps and limits, choose the control mode, then configure the I/O. In order:

  1. Motor nameplate data: voltage, current, frequency, speed and power. Wrong nameplate values are the most common cause of poor drive behaviour.
  2. Ramps: acceleration and deceleration times in seconds.
  3. Limits: minimum and maximum frequency, and current limit.
  4. Control mode: V/Hz for simple fans and pumps; sensorless or closed-loop vector control for higher torque at low speed. Wikipedia notes V/Hz control is sub-optimal in high-performance applications.
  5. I/O: analogue speed reference, digital start/stop, relay outputs, or a fieldbus command word.

Three practical cautions from Wikipedia's article on VFDs: motor cooling deteriorates as speed decreases, so prolonged low-speed running at significant torque may need a separately powered cooling fan; pulses can reflect back from the motor terminals into the cable, with a recommended maximum distance of about 50 m for 460 V or 575 V systems using third-generation IGBTs unless filters are fitted; and braking energy is dissipated as heat in braking resistors via a braking chopper. Always follow the drive manufacturer's installation manual for cable, filter and earthing requirements.

How do you size and select a drive?

Size the drive on the motor's full-load current as well as its power rating, and match it to the load type. A drive rated in kilowatts only is not enough: check the continuous output current against the motor nameplate current, and check the overload capability against the duty. Fans and pumps usually need modest overload capacity, while conveyors starting under load, crushers or extruders need more starting torque and a higher overload rating.

Questions to settle before ordering:

  • Load type: variable torque, constant torque or constant power (see the table above).
  • Speed range and torque at low speed: this decides between V/Hz and vector control, and whether the motor needs forced cooling.
  • Braking: does the load regenerate (a high-inertia fan, a downhill conveyor, a hoist)? If so, the drive needs a braking chopper and resistor, or a regenerative front end, or it will trip on DC bus overvoltage.
  • Cable length and filters: long motor cables may need output filters, per the manufacturer's installation manual.
  • Safety: if the drive removes torque as part of a stop or guard function, choose a drive with a built-in safe-torque-off input and validate the whole function against ISO 13849-1 with your safety engineer.
  • Communication: the fieldbus your PLC uses, and a plan for loss of communication.

What goes wrong most often with VFDs?

Most field problems are setup problems rather than hardware faults. The common ones are wrong motor data, ramps set too short for the inertia (causing overcurrent or overvoltage trips), a speed reference scaled incorrectly between PLC and drive, local and remote control modes left in the wrong state, and motors run slowly for long periods without extra cooling. Electrical noise from the drive's switching can also upset low-level analogue signals, so keep motor cables away from instrument cables and follow the manufacturer's earthing guidance. Read the drive's fault history before you change any parameters, because it tells you what actually happened.

How does a VFD connect to a PLC?

Either hard-wired or over a network. Hard-wired is a 0-10 V or 4-20 mA speed reference plus digital start and stop. A network connection (PROFINET, EtherNet/IP or Modbus TCP) lets the PLC send the setpoint and control word, and read actual speed, current and fault codes. Network control saves wiring and adds diagnostics, but you must decide what the drive does if communication is lost. For PROFINET design basics see the PROFINET guide, and for the energy side of the business case see energy management and ISO 50001.

How EDWartens can help

The Professional Module is a five-day live online class in Siemens TIA Portal: PLC logic, HMI and WinCC SCADA. Drive parameterisation itself is not a day-by-day topic of the class, but the PLC and PROFINET skills it builds are what you use to command a drive, and the self-paced Basic Engineering modules cover electrical engineering and control systems. The class is online and Siemens-focused. For practice, use the free motor control simulator and the industrial motor control course. Details: Professional Module and sign up.

Start free

Learn electrical and control panels free, then practise the job

Free job simulation

Control Panel Design Engineer

GA drawing, schematics, BOM, heat calculation and the routine test.

The first five days are free, no card needed.

Live UK jobs

Electrical design jobs in the UK

Updated daily, with licensed visa sponsors marked.

Browse all engineering jobs

Frequently asked questions

How much energy does a VFD save on a pump or fan?

On centrifugal fans and pumps, power varies with the cube of speed, so the Carbon Trust says a 20% speed reduction can save around 50% of power. The saving is smaller on constant-torque loads such as conveyors, and on pumps with a high static head, so size the benefit from the actual duty cycle.

What is the difference between V/Hz and vector control?

V/Hz (scalar) control keeps voltage proportional to frequency and is simple and adequate for most fans and pumps. Vector control models the motor's flux and torque, giving better torque at low speed and faster response, which suits cranes, extruders and similar loads. Wikipedia notes V/Hz control is sub-optimal in high-performance applications.

Can a VFD run a motor below its normal speed all the time?

Yes, but motor cooling deteriorates as speed falls, so sustained low-speed running at significant torque can overheat a self-cooled motor. Options include derating, a separately powered cooling fan, or an inverter-duty motor. Check the motor and drive manufacturers' guidance for the speed range and torque you need.

How does a PLC control a VFD?

Either through hard-wired signals (a 0-10 V or 4-20 mA speed reference plus digital start and stop) or over a network such as PROFINET, EtherNet/IP or Modbus TCP. A network lets the PLC send setpoints and control words and read actual speed, current and fault status, but you must define the drive's behaviour on communication loss.

Why does a VFD need the motor nameplate data?

The drive uses rated voltage, current, frequency, speed and power to set its V/Hz relationship, current limits and motor model. Wrong values cause poor torque, nuisance trips or overheating. Always enter the data from the motor's nameplate, and run any auto-tune routine the drive offers once the wiring is finished.

Sources

  1. Variable speed drives: introducing energy saving opportunities for business (CTG006), Carbon Trust, hosted by GAMBICA
  2. Adjustable Speed Drive Part-Load Efficiency, Motor Systems Tip Sheet 11, US Department of Energy
  3. Variable-frequency drive, Wikipedia
  4. Affinity laws, Wikipedia
  5. Induction motor, Wikipedia

Share this article

About the author

EDWartens Team

EDWartens Instructional Team

The EDWartens instructional team brings together UK-based automation engineers, certified Siemens and Rockwell specialists, and industry practitioners with decades of combined experience in PLC programming, SCADA engineering, and industrial AI.

View all articles by EDWartens

Ready to become job-ready?

Start with a free course today, or train live in Siemens PLC, HMI and SCADA on the Professional Module.

Related articles

Career

VR Training for Industrial Automation: What the Evidence Shows

A meta-analysis of virtual, augmented and mixed-reality training found it as effective as traditional methods, not better, with its value lying where danger or cost rules out the real thing. For PLC programming, desktop simulation such as PLCSIM and Factory I/O covers most needs; headsets earn their place in safety and spatial tasks.

Read article
Physical AI

What Is a PLC and Why Learn It? A UK Guide (2026)

A PLC (programmable logic controller) is a ruggedised industrial computer that reads sensors, runs a stored program in a repeating scan, and switches motors, valves and lights. UK permanent PLC Engineer adverts quoted a median of £60,000 in the six months to 21 October 2026, according to ITJobsWatch.

Read article
Physical AI

Industrial Sensors Guide: Types, Signals and How to Choose

An industrial sensor turns a physical quantity into an electrical signal a PLC can read: either a discrete on/off switch or an analogue signal, most often 4-20 mA. Choose by what you measure, the target material, range, environment and output type. A 4-20 mA loop treats anything below 3.8 mA as a fault, which makes broken wires easy to spot.

Read article
Physical AI

Industrial Actuators Explained: Motors, Valves and Cylinders

Actuators turn a PLC output into physical motion using electric, pneumatic or hydraulic energy. Industrial pneumatics typically run at about 80 to 100 psi, while hydraulics commonly work at 1,000 to 5,000 psi, which is why hydraulics are chosen when force is the priority. Match the actuator to force, speed, precision and the PLC interface.

Read article